SKDP13A-M485-S1 Temperature & Humidity Transmitter, RS485 Modbus RTU
SKDP13A-M485-S1 Temperature & Humidity Transmitter, RS485 Modbus RTU
Product Images
SKDP13A-M485-S1 Temperature & Humidity Transmitter, RS485 Modbus RTU
SKU: GC-ATC-SKDP13A-M485-S1
MPN: SKDP13A-M485-S1
ATC
Free shipping to the continental US on orders over $100
Stock Status: In stock
Product Description
The SKDP13A-M485-S1 measures air temperature and relative humidity. It shows both readings on a front-panel LED display and reports them to your PLC, SCADA system, or building controller over RS485 using Modbus RTU.
Inside is a Sensirion SHT40 sensor rated at ±0.2°C (±0.36°F) and ±1.8%RH at 25°C (77°F). Both values resolve to 0.1 units and update every second. The probe is built into a wall-mount housing, so installation takes four screws and four wires.
All configuration can be done at the device or over the bus. Use the two front-panel keys to set the Modbus server address, baud rate, display unit (°C or °F), and offset corrections, or write the same settings to holding registers. Settings are kept when power is removed.
Typical uses include telecom and server rooms, warehouses, livestock and agricultural buildings, and any site where an RS485 controller needs a local, readable temperature and humidity point.
Features
- Sensirion SHT40 sensor: ±0.2°C (±0.36°F) and ±1.8%RH accuracy at 25°C (77°F)
- Dual LED display shows temperature and humidity at the same time
- RS485 interface with standard Modbus RTU (function codes 03, 06, and 16)
- Modbus server address can be set from 1 to 254, so many units can share one bus
- Baud rates from 1,200 to 115,200 bps (default 9,600 bps, 8N1)
- Display and register output switch between °C and °F
- Field-adjustable offsets for temperature (±10.0°C/°F) and humidity (±10.0%RH)
- Setup from the front-panel keys or over Modbus, kept through power loss
- COM LED flashes during RS485 traffic for quick wiring checks
- Draws less than 10 mA, so it adds little load to a shared 24 VDC supply
- Sensor fault reporting: returns 0x7FFF if the sensor is missing or damaged
- Wall-mount enclosure with four mounting tabs and a cable gland entry
Documents and Drivers
Documentation
User Manual
Specifications
Measurement
- Sensor: Sensirion SHT40, built-in probe
- Temperature range: -20°C to 70°C (-4°F to 158°F)
- Humidity range: 0 to 100%RH
- Temperature accuracy: ±0.2°C (±0.36°F) at 25°C (77°F)
- Humidity accuracy: ±1.8%RH at 25°C (77°F)
- Temperature resolution: 0.1°C (0.18°F)
- Humidity resolution: 0.1%RH
- Sensitivity: temperature below 0.1°C (0.18°F); humidity below 0.1%RH
- Sampling rate: 1 second
Communication
- Interface: 1 × RS485
- Protocol: Modbus RTU
- Default serial settings: 9,600 bps, no parity, 8 data bits, 1 stop bit
- Supported baud rates: 1,200 / 2,400 / 4,800 / 9,600 / 19,200 / 38,400 / 57,600 / 115,200 bps
- Server address range: 1 to 254 (default 1)
- Function codes: 03 (read), 06 (write single), 16 (write multiple)
Electrical
- Supply voltage: 10 to 30 VDC (24 VDC nominal)
- Current consumption: less than 10 mA
- Wiring: 4-wire. VDD = red (brown), GND = black (yellow), RS485-A = white (green), RS485-B = yellow (blue)
Configuration
- Temperature correction: -10.0 to +10.0 (in the selected unit, °C or °F)
- Humidity correction: -10.0 to +10.0%RH
- Display unit: °C or °F, selectable
Mechanical
- Mounting: wall mount, 4 tabs
- Housing dimensions (excluding probe and cable gland): 105 × 85 × 41 mm (4.13 × 3.35 × 1.61 in)
- Mounting hole spacing: 100 × 75 mm (3.94 × 2.95 in)
- Display: dual 3-digit LED (humidity and temperature)
- Indicators: COM (RS485 activity)
FAQs
Which Modbus registers hold the temperature and humidity readings?
Read temperature from holding register 40001 and humidity from 40002 using function code 03. Both values are scaled by 10, so divide the raw register value by 10 to get the actual reading. For example, a raw value of 253 equals 25.3°C (or °F if Fahrenheit is selected), and 651 equals 65.1%RH.
What are the default communication settings, and how do I change the server address?
The transmitter ships at Modbus server address 1, 9,600 bps, no parity, 8 data bits, and 1 stop bit. To change the address, press the up and down keys together to enter the settings menu, adjust the value, and press both keys again to save. You can also write a new address (1–254) to register 40019 and a new baud rate code to register 40020 using function code 06 or 16. Give each device on a shared bus its own address.
Can the transmitter report in Fahrenheit?
Yes. Set the temperature unit from the front-panel menu or write to register 40021 (0 = Celsius, 1 = Fahrenheit). The selected unit applies to both the LED display and the Modbus temperature register. The temperature correction value in register 40022 is also applied in the selected unit.
How do I calibrate or offset the readings in the field?
Use the temperature correction (register 40022) and humidity correction (register 40023) to apply an offset of -10.0 to +10.0 in 0.1 steps. You can set both from the front-panel menu, too. Offsets are saved and kept through power cycles, so you can match the transmitter to a reference instrument once and leave it.
What does a reading of 0x7FFF mean?
The transmitter returns 0x7FFF (32767) when it cannot detect the temperature and humidity sensor or the sensor is damaged. Set your controller or SCADA logic to treat this value as a fault condition rather than a measurement, so a failed sensor raises an alarm instead of logging bad data.
Why Choose Us
Feel confident from search to shipment
We're committed to making your experience simple, transparent, and reliable. With customer-first guarantees and expert support, Grid Connect helps you choose the right solution with confidence.
Reviews
Have a Special Request?
What you can expect from Grid Connect:
- High quality industrial networking and IoT solutions.
- Hundreds of product options to fit your needs, many available to ship same or next day.
- Unmatched technical support.
- Customization options to fit your needs.
- Price match guarantee on all products.